ACQ580_Water & Waste Water Drives

    ACQ580_Water & Waste Water Drives

    ACQ580

    Brand: ABB

    Category: AC Drives

    Description

    The ACQ580-31 offers full water functionality with a clean supply (THDi less than 3%), easily meets harmonic standards, and simplifies system design by eliminating the need for overdimensioned components. Its straightforward installation with no external hardware improves system efficiency and reduces overall costs. ACQ580-31 offers you full water functionality and clean supply with THDi less than 3%.

    Specifications

    Power Rating:From 0.75 to 500 kW
    Voltage:From 200 to 480 V (+10%/-10%)

    Need installation or commissioning support?

    View our services

    ACQ580_Water & Waste Water Drives overview

    The ABB ACQ580 is a drive built for water and wastewater pumping. It has the ACS580 hardware platform with pump-specific software, so features that usually need a PLC are built in.

    Pump functions built in

    • Multipump control: run up to several pumps in parallel with alternation and cascading to share wear.
    • Level control for tanks, wet wells and lift stations.
    • Soft pipe fill to avoid water hammer when starting into an empty pipe.
    • Dry-run and pump protection to stop the pump on loss of suction or abnormal load.
    • Pump cleaning (forward/reverse sequences) to clear ragging in sewage pumps.
    • Flow calculation without a separate flowmeter, and energy savings counters.
    • PID control with sleep and boost for pressure boosting.

    For installations with strict harmonic limits or generator supply, the ACQ580-31 ultra-low harmonic version offers THDi below about 3% without external filters.

    Sizing

    Use the pump motor nameplate current and normal-duty rating for centrifugal pumps. Positive displacement and progressive cavity pumps are constant torque — size them on the heavy-duty rating.

    Typical applications

    • Water supply and booster pumping stations
    • Sewage lift stations and wet wells
    • Water and sewage treatment plants (STP/ETP/WTP)
    • Irrigation pumping
    • Borewell and submersible pumps

    Selection tips

    • Use normal-duty rating for centrifugal pumps, heavy-duty for PD pumps.
    • Choose ACQ580-31 when harmonic limits or DG supply apply.
    • Use built-in multipump instead of a PLC for simple duty/standby sets.
    • Check cable length to submersible pumps; long cables may need output filters.

    ACQ580_Water & Waste Water Drives: frequently asked questions

    What is the difference between ACQ580 and ACS580?

    They share hardware, but the ACQ580 has water-specific software: multipump, level control, pipe fill, dry-run protection and pump cleaning.

    Can one ACQ580 control several pumps?

    Yes. Multipump functions coordinate several pumps with alternation, so a duty/assist/standby set can run without a separate PLC.

    Can the ACQ580 run submersible pumps?

    Yes. Check motor cable length and the pump's minimum speed requirement; we can advise on output filters and settings.

    How do I select a VFD for a pump?

    Read our step-by-step guide on selecting a VFD for pump applications, or send us the pump and motor data for a sizing recommendation.

    Related guides

    Related AC Drives (VFDs)

    ACS-AP-S Assistant Control Panel

    ACS-AP-S

    ACS-AP-S Assistant Control Panel

    Brand: ABB

    Specifications:

    • •Power: Basic Assistant Control Panel
    FEIP-21 Ethernet/IP Module

    FEIP-21

    FEIP-21 Ethernet/IP Module

    Brand: ABB

    Specifications:

    • •Power: Ethernet/IP Communication
    ACS560 - General Purpose Drives

    ACS560-01-xxxx-4

    ACS560 - General Purpose Drives

    Brand: ABB

    Specifications:

    • •Power: 0.75 to 160 Kw
    • •Voltage: From 380 to 480 V (+10%/-10%)